CK720                            
*     CGH_Tech  
      CK720  
                               
   
  Logons Navigating a CK370 Commissioning a CK370
  Events
  IP's (ZMP) A sample of the P2000 Server items that cannot be retrieved  from the CK720/721 User Interface:
  Trackvia 1 P2000 System Events
  Aiphones 2 Users Logins and Permissions
  CK720 3 Cardholder Database Names (Only the Badge Numbers can be viewed in the User Interface)
  Pegasys1500 4 Access Group Names (The User Interface lists Access Groups by numbers only)
  db_flash 5 Terminal Groups (Used at some sites to refine Access Groups)
    6 P2000 Workstation Names
   
   
    You will need the following to complete this task:
    1) A Laptop Computer or Desktop PC.
   
    2) A VT100 Serial Connection such as Tera Term  (if the CK720/721 IP Address is unknown) IP Address is unknown
    OR
    3) A Network Connection using Telnet (if the CK720/721 IP Address is known) IP Address is known
   
   
    Login to CK720-721
    login:   CK720
    psswd:   master
   
   
   
    User Interface Main Page:  
   
   
   
   
   
   
   
   
   
   
    Main
    Page
    1 Copy and Paste the Main Page screenshot to a folder Try "Logging" vs  Copy and Paste !!
    Panel 2 Highlight Panel then <enter>
    3 Copy and Paste the Panel Parameters screenshot to a folder
    4 Press <esc> to return to the User Interface Main Page
   
    Terminal 5 Highlight Terminal then <enter>
    6 Copy and Paste the Terminal Number screenshot to a folder
    7 Enter a Terminal Number (Example 1) then <enter>
    1 1 Copy and Paste Page 1 of the Terminal Parameters Data screenshots to a folder
    2 Highlight <Page Down> then press <enter>
    3 Copy and Paste Page 2 of the Terminal Parameters Data screenshots to a folder
    4 Highlight <Page Down> then press <enter>
    5 Copy and Paste Page 3 of the Terminal Parameters Data screenshots to a folder
    6 Highlight <Page Down> then press <enter>
    7 Copy and Paste Page 4 of the Terminal Parameters Data screenshots to a folder
    8 Highlight <Next Record> then press <enter>
   
    Repeat the above steps for all remaining Terminals then press <esc> to return to the User Interface Main Page
   
    Output 8 Highlight Output then press <enter> A new page opens showing all Terminals containing Output Points
    9 Copy and paste the Terminal Number screenshot to a folder
    10 Type a number for a Terminal then press <enter>     (ie 3)
    3
    11 Copy and paste the Terminal Number screenshot to a folder
    12 Type a number for a Terminal then press <enter>
    13 Copy and Paste this screenshot to a folder
    14 Type the number for a specific Output Point then press <enter>
    15 Copy and Paste the Output Point  Parameters screenshot to a folder
    16 Highlight <Next Record> then press <enter>
    17 Copy and Paste the Output Point  Parameters screenshot to a folder
    18 Highlight <Next Record> then press <enter>
   
    Repeat the above steps for all remaining Outputs then press <esc> to return to the User Interface Main Page
   
    Input 19 Highlight Input then press <enter> A new page opens showing all Terminals containing Input Points
    20 Copy and Paste the Terminal Number screenshot to a folder
    21 Type a number for a specific Terminal then press <enter> A new page opens showing all Input Points associated with the selected Terminal
    22 Copy and Paste the Input Point Number screenshot to a folder
    23 Type a number for a specific Input Point then press <enter>
    24 Copy and paste the Input Point Parameters Data Entry screenshot to a folder
    25 Highlight <Next Record> then press <enter>
   
    Repeat the above steps for all remaining Inputs then press <esc> to return to the User Interface Main Page
   
    Panel Soft Alarm 26 Highlight Panel Soft Alarm then press <enter>
    27 Copy and Paste the Panel Soft Alarm Parameters screenshot to a Folder
    28 Press <esc> to return to the User Interface Main Page
   
    Timezone 29 Highlight Time Zone then press <enter>
    30 Copy and paste the Timezone Number screenshot to a folder
    31 Type a number for a Time Zone then press <enter>
    32 Copy and Paste the Timezone Data Entry screenshots to a folder
    33 Highlight < Next Record> then press <enter> to navigate
    34 Repeat for all remaining Timezones
   
    Badge 35 Highlight Badge then press <enter>
   
    IMPORTANT NOTE:  The Badge Data can only be viewed if you have access to the Facility Badge Numbers.  Names/Department/Company etc. is not available in the User Interface 
    Other information such as Cardholder Names/Department/Company etc. is not available in the User Interface.
   
    36 Enter a Start Badge Number
    37 Enter an End Badge Number
    38 Copy and Paste the Badge Parameters Data screenshot to a folder
    39 Highlight <Next Record> then press <enter>
   
    Repeat the above steps for all remaining Badges then press <esc> to return to the User Interface Main Page
   
    System Info'n 40 Highlight System Information then press <enter>
    41 Copy and paste the System Information screenshots to a folder
    42 Press <esc> to return to the User Interface Main Page
   
    Access Group 43 Highlight Access Group then press <enter>
    44 Enter a number for a specific Access Group then press <enter>
    45 Copy / Paste Access Group Parameters Data screenshot to a folder
    46 Highlight <Next Record> then press <enter>
    47 Repeat the above steps for all remaining Access Groups
    48 Press <esc> to return to the User Interface Main Page
   
    Route Info 49 Highlight Route Info then press <enter>
    50 Copy and paste the Route Info screenshot to a folder
    51 Press <esc> to return to the User Interface Main Page
   
    Log Out Highlight Log Out then press <enter>
   
   
    The Data extracted from the CK720/721 User Interface can now be manually entered into a blank P2000 Database.